欧美日韩熟妇中文字幕_中文字幕不卡av一区_无遮挡十八禁污污网站免费_综合综色精品无码_在线精品国产专区_亚洲一成Av人片乱码色午夜_国产精选热在线观看_网友分享国产色诱美女免费视频心得_了解最新久久成人十八免费网站_日本三级带黄在线观看直播

Hotline:0411-85621575
Home ProductsHigh-voltage switch equipmentKYN28-12 steel-clad movable AC metal-enclosed switchgear

KYN28-12 steel-clad movable AC metal-enclosed switchgear

KYN28-12 steel-clad movable AC metal-enclosed switchgear (hereinafter referred to as “switchgear”) applies to three-phase AC 50Hz, .3.6 ~ 12Kv power system for receiving and distributing electric energy and control, protection and testing of the circuit.
 
■ Standards
GB3906 (3 ~ 35kV AC metal-enclosed switchgear). GB/T11022 (common technical requirements on high-voltage switchgear and control equipment standards), IEC60298 (rated voltages above 1kV and below 50kV AC metal-enclosed switchgear and control equipment), DL / T404 (technical conditions on indoor AC high voltage switchgear ordering).

■ Model meaning


■ Normal service conditions
● The ambient air temperature: maximum temperature at +40 ℃, the lowest temperature -15 ℃;
● humidity: daily average relative humidity: ≤ 95%, the daily average vapor pressure not exceeding 2.2kPa, monthly mean relative humidity: ≤ 90%, the monthly average vapor pressure not exceeding 1.8 kPa;
● Altitude: 3000m and below; 
● Earthquake intensity: not more than Degree 8;
● ambient air is not polluted by corrosive or flammable gases, or water vapor;
● At places with no recurrent severe vibration;
● When used in conditions beyond the normal environmental conditions prescribed in GB3906, solutions shall be found through negotiation between users and the manufacturer.
■The main technical parameters

Item

 

 

unit

data

Rated voltage

 

 

KV

3.6、7.2、12

Rated power

 

 

Hz

50

Rated current of circuit breaker

 

 

A

630、1250、1600、2000、2500、3150

Switchgear rated current

 

 

A

630、1250、1600、2000、2500、3150

Rated short-time withstand current(4s)

 

 

kA

16、20、25、31.5、40

Rated short-time withstand current (peak)

 

 

kA

40、50、63、80、100

Rated short-circuit breaking current

 

 

kA

16、20、25、31.5、40

Rated short-circuit making current (peak)

1min power frequency withstand voltage

 

kA

40、50、63、80、100

Rated insulation level

lightning impulse withstand voltage (peak)

interelectrode, phase to earth

kV

24、32、42

Between open contacts

kV

24、32、48

 

interelectrode, phase to earth

kV

40、60、75

between open contacts

kV

46、70、85

Protection class

 

 

Outside the lightIP4X、Isolation, the circuit breaker compartment door open for theIP2X

Structural features
● switching device structure shown in Figure 1;
● Full metal enclosed, assembly structure, a wide range of combination scheme;
● cabinet made of imported aluminized galvanized steel sheet after CNC machining using advanced multi-folding process, connected with rivet nut and high-strength bolt, marked by high precision, corrosion resistance, light weight, high strength, general-purpose parts;
● it can be equipped with domestic VS1 series or imported VD4 series vacuum circuit breaker, with wide applicability and high reliability, maintenance-free for years;
● handcart has working and test positions, location and display device for the positions ensures safety and reliability.
●various handcarts accord with modular change by modulus to ensure the handcart with the same specification can be freely interchangeable and the handcart of different specifications must not enter;
● handcart transported by special trucks, simple and flexible operation;
● cable compartment can install up to nine single-core cables;
● Highly reliable interlock, fully meeting the “Five-prevention” requirements;
● The high-voltage chamber has pressure relief channel to ensure personal safety;
● front door equipped with observation windows to observe working condition of interior components.

■ switchgear structure diagram



■ Dimensions


Height B

 

2300(2200)(mm)

Width A

rated current of branch miniature bus up to 1250A, thermal current 40KA

800(mm)

rated current of branch miniature bus above 1600A

1000(mm)

Depth C

cable inlet and outlet

1500(mm)

Overhead inlet and outlet

1660(mm)